You can add the Hardware Scan Service in any JACE controller running AX-3.7 or later. To add the service, simply install two software modules, using the Software Manager in a platform connection:
platHwScan (always necessary), plus:
platHwScanType
where Type varies by the specific JACE model series (see below). If you select only the platHwScanType module, the required platHwScan module becomes automatically selected.
Installing these modules results in a reboot of the JACE controller.
Figure 2 shows the two modules selected that are necessary for a JACE-2, JACE-3E, JACE-6, or JACE-6E series controller. By controller series, platHwScanType is as follows:
Table 1. platHwScanType module needed, by controller model series
| Controller Series | platHwScanType module
|
|---|---|
| JACE-2/6 (200/600), JACE-3E, JACE-6E | platHwScanNpm |
| JACE-7 (700) | platHwScanJvln |
| JACE-603 (JACE-403 with retrofit board) | platHwScanJ603 |
| JACE-645 (JACE-545 with retrofit board) | platHwScanJ645 |
| JACE-x02 Express (202/602-XPR or M2M) | platHwScanXpr |
| JACE-NXS/NXT | platHwScanNx |
| Security JACE (201/601) | platHwScanSec |
If you install the incorrect platHwScanType module, or install only platHwScan module, the default view on the station’s Hardware Scan Service will simply display:Jar file platHwScanType is required to support this platform In this case, simply install the correct type using the table above.
Copyright © 2000-2014 Tridium Inc. All rights reserved.