kitControl-OutsideAirOptimization

 OutsideAirOptimization is available in the kitControl Energy folder. The OutsideAirOptimization component is used to support applications that need to allow for enthalpy based free cooling. This object is typically used during occupancy periods.

The freeCooling output is set to false if outside >= inside and set to true if outside <= inside - (abs) thresholdSpan. You can select temperature or enthalpy comparisons. There is also a low temperature check to protect against freezing.

Setup of the object involves the following properties (also see Example 13), as follows:

Example 13. Using OutsideAirOptimization

An example OutsideAirOptimization component usage is shown in Figure 39.

Figure 39. Example OutsideAirOptimization


Example OutsideAirOptimization



See also Alphabetical list of kitControl components