Using Quik Learn for a new LonNetwork

Typically, you use the “Quik Learn” (spelling intentional) function in the Lon Device Manager to populate your new LonNetwork with the proper LonDevice components. This function is useful for both previously “managed” and “unmanaged” Lonworks networks, further defined as follows:

To populate a new network from previously managed network

Perform this task to populate a new LonNetwork in your station database, where existing Lon network management is preserved.

To populate your new LonNetwork:

  1. Double-click the LonNetwork to bring up the Lon Device Manager.

    NoteIf in split-pane (learn mode), click the Learn Mode tool  to toggle out of learn mode.

  2. Click the Quik Learn  button.

    A popup Learn dialog appears.

  3. In the Learn dialog, leave the top option cleared, and either check (or clear) the bottom options “Learn Links: add links to the database ” and “Upload Config: upload ncis and cps ”, and click OK.

    A progress bar appears at the top of the view, and updates as the Lon Learn occurs.

  4. When the learn job completes, learned Lon nodes are listed in the “Database” table. All devices should appear listed with unique subnet/node addresses.

    • If you chose to learn links, you can see any learned bindings in other views of the LonNetwork, including the Lon Link Manager view or (graphically) in the network’s wire sheet view.

    • If you chose to upload config, you can see the values of any device’s ncis from its Nc Manager view (right-click the device and select ViewsNc Manager).

  5. You can create Lon proxy points under any device. See Create Lon proxy points.

To populate a new network from previously unmanaged network

Perform this task to populate a new LonNetwork in your station database, where Niagara applies unique and contiguous subnet-node addressing to learned devices.

To populate your new LonNetwork:

  1. Double-click the LonNetwork to bring up the Lon Device Manager.

    NoteIf in split-pane (learn mode), click the Learn Mode tool  to toggle out of learn mode.

  2. Click the Quik Learn  button.

    A popup Learn dialog appears.

  3. In the Learn dialog, check “Unmanaged Network: ignore subnet/node conflicts,” and (typically) “Upload Config: upload ncis and cps ”, and click OK.

    A progress bar appears at the top of the view, and updates as the Lon Learn occurs.

    When the learn job completes, learned Lon devices are listed in the “Database” table.

  4. Click to select all devices, and click the Commission  button.

    A progress bar appears at the top of the view, and updates as the Lon Commission occurs. See Commission for more details.

  5. When the commission job completes, all devices should appear listed with a “Config Online” state, and with unique subnet/node addresses.