Configuring a Tuning Policy

  1. In the JciN2Network's property sheet, expand Tuning Policies to see one or more contained Tuning Policies.

  2. Expand the desired Tuning Policy to see the configuration properties.

  3. Edit the configuration properties using Table x as a reference.

    JciN2Network Tuning Policy Properties Guidelines

    Configuration Property

    Monitor Only Inputs

    Critical Hardware Inputs Used for Slave or FX Supervisory Control Logic

    Network Variable Inputs Connected to Critical Shared Hardware Inputs (Process Variables Used in Control Logic)

    Network Variable Inputs: Non-Critical Shared Hardware Inputs (OA-T, Occupancy Schedule)

    Network Variables Used for Setpoints

    Internal Module Relinquish Default

    Min Write Time

    N/A

    N/A

    0 (default)

    10 minutes

    0 (default)

    0 (default)

    Max Write Time

    N/A

    N/A

    1 minute

    20 minutes

    20 minutes

    0 (default)

    Write on Up

    N/A

    N/A

    True (default)

    True (default)

    True (default)

    False

    Write on Start

    N/A

    N/A

    True (default)

    True (default)

    True (default)

    True (default)

    Write on Enabled

    N/A

    N/A

    True (default)

    True (default)

    True (default)

    False

    Stale Time

    0 (default)

    0 (default)

    0 (default)

    0 (default)

    0 (default)

    0 (default)

  4. Click Save.