The Data Recovery Service Editor is the default view on the DataRecoveryService, as found in the PlatformServices of the following JACE controllers:
A JACE-3E series controller (based on the NPM3 processor, with built-in SRAM). This model was introduced in 2013, around the time of a NiagaraAX-3.7 update release (build 3.7.105).
A JACE-6E series controller (based on the NPM6E processor with built-in SRAM). This model was introduced in early 2012, around the time of a NiagaraAX-3.6.44 maintenance release.
A JACE-603 or JACE-645 controller configured for NiagaraAX (and not Niagara R2). These “retrofit board” JACEs are also based on the NPM6E processor, and supported in build 3.6.44 or later.
A JACE-2,-6,-7 series or JACE-x02 Express (XPR or M2M) series controller, with an installed “SRAM option card”.
This view allows monitoring of the “battery-less” support provided by this service. Starting in build 3.6.44, an SRAM-equipped JACE can additionally (and optionally) use a backup battery—such as an NiMH onboard battery pack, and (if applicable) and external 12V sealed lead-acid battery. In this case, both the DataRecoveryService and PowerMonitorService can exist in the station’s PlatformServices container, operating independently or in unison, as configured.
For details, see the “About the DataRecoveryService” section in the Engineering Notes II document JACE Data Recovery Service (SRAM support).