Click the drop-down control
in the Host field and select Tunnel (IP)
In the top Host Tunnel (IP) field, enter the IP address or hostname of the Supervisor (the tunnel proxy server). In the example shown below, the Supervisor is at 192.168.1.37 IP address.
In the Port field, enter the configured Http Port property value in the Supervisor’s WebService, where 80 is the standard (default) value.
In the Tunnel to field, enter either:
IP address or hostname of the endpoint JACE platform, if “Only Tunnel Known Stations” is false in the FoxService of the NiagaraNetwork of the Supervisor. (Figure C.5, left), or
Station name of the station associated with the endpoint JACE, if “Only Tunnel Known Stations” is true in the FoxService of the NiagaraNetwork of the Supervisor. (Figure C.5, right).
For related details, see FoxService settings for platform tunneling.
If the endpoint JACE platform is using a “non-standard” HTTP port for the platform daemon, meaning not port 3011, append a colon (:) and that port number on the “Tunnel to” value. For example:
192.168.1.88:3012 (if the JACE is using port 3012 for the platform daemon)
In the Credentials fields (Username and Password), enter the JACE’s platform credentials .
Copyright © 2000-2014 Tridium Inc. All rights reserved.